Ultrasonic Liquid Flow Meter

SLF500
  • SLF500

Small and compact design, contamination free clamp-on ultrasonic flow meter

・Easy handling and installation to existing pipes
・Low power consumption
・Wide measurement range

LINE UP
  • SLF-100
  • SLF-500
SPECIFICATIONS
■Ultrasonic Liquid Flowmeter SLF Series

SLF-100

Converor
Model SLF-100
Measurement method Ultrasonic transit time method
Environment conditions Temperature:-10〜50℃ 
Display function LCD display(16characters× 2lines)                Instantaneous flow rate, or Integrated flow rate 
Configuration menu Measurement range, Measurement unit, etc. 
Accuracy ±2%RD(flow speed 1〜10m/s)
±2cm/s(flow speed less than 1m/s) 
Output Analog output  DC 4〜20mA, load resistance: less than 450Ω
Pulse Open collector standard 30V, 0.25A
Alarm Open collector standard 30V, 0.25A
Power supply DC12~30V
Power dissipation less than 2.5VA
Weight Approx. 330g
Sensor
Model SLT-12, SLT-14, SLT-15
Structure Clamp-on type 
Material PVC、PTFE 
Applicable liquid de-ionized water, chemical solution
Applicable pipes Nominal diameter  SLT-12: 3/4 inch(I.D.15.88 O.D.19.05),
1/2inch (I.D.9.53 O.D.12.70),
3/8inch (I.D.6.35 O.D.9.53)
SLT-14: 3/4inch (I.D.15.88 O.D.19.05),
1/2inch (I.D.9.53 O.D.12.70)
SLT-15: 1inch (I.D.22.23 O.D.25.4),
3/4inch (I.D.15.88 O.D.19.05) 
Material PFA
Environment conditions of flow SLT-12:10~60℃
SLT-14:10~70℃
SLT-15:10~50℃
Cable 5m(max 10m)
Measurement range 0.5〜230L/min(1 inch),
0.2〜120 L/min(3/4 inch),
0.1〜40 L/min(1/2 inch),
0.1〜20 L/min(3/8 inch)
Weight SLT-12 Approx. 450g
SLT-14 Approx. 350g
SLT-15 Approx. 360g
■Ultrasonic Liquid flowmeter SLF Series

SLF-500

Converor
Model SLF-500
Measurement method Ultrasonic transit time method
Accuracy ±2%RD (1〜10m/s), ±2cm ( 0〜1m/s) 
Applicable liquid Water and other liquids (input of sound speed) 
Liquid temperature 0~60℃ 
Applicable pipes Nominal diameter 15mm〜300mm (External diameter more than 20mm )
Material PVC, SUS and others(input of sound speed) 
Analog output range 0〜1m/s and 0〜10m/s 
Damping Standard 10 sec (range 0〜20 sec, 1sec steps)
Structure Waterproof type (IP65 equivalnet) 
Material ADC12
Installation temperature 0~+50℃
Installation humidity  No condensation
Power supply AC85~264V 50/60Hz
Power dissipation less than 2.5VA 
Analog output  Output contents Instantaneous flow rate (normal/reverse flow)
Output signal DC4~20mA
Load resistance  less than 450Ω
Output constant 0〜20sec (1sec steps) 
Flow rate low cut 0〜10% (1% steps)
Pulse output Output contents  normal/reverse flow Integrated pulse,
abnormal, upper/lower flow limit.
Output signal Open collector x3
Standard DC30V 0.25A
Integrated units 0.1L, 1L, 10L, 100L, 1m3 ,10m3
Pulse width 1.6msec or 50msec
Intecrated low cut  0〜10% ( 1% steps)
Digital output Output cpntents instantaneous flow rate, integrated flow, alarm 
Serial interface RS-232C 
Display LCD display 16 characters × 2 lines
Display menu instantaneous flow, integrated flow
Configuration items FS flow, flow rate unit, integrated flow unit, and others 
Sensor probe
Model SLT-20S
Material PEEK, SUS304
Structure Clamp-on type
Installation V or Z type
Installed temperature  -20~+60℃
Cable Standard 10m 1.5C-QEV (Max. 30m)
Weight Approx. 400g
Installation conditions Upper stream side 10D, Lower stream side 5D or more (D is inner diameter)